机房巡检,两台Radware 8016面板上的FAN只指示灯亮红灯。如何确认是否是风扇硬件故障?
一、开启告警日志实时弹出
#manage terminal traps-output set 2(或on)
HNCS-PC-IDC-SSL02-8018#24-11-2014 09:31:47 WARNING Fan failure was detected. 1 fan is not operational
二、开启日志记录
#manage trap-logging status set 1 /*开启日志记录
#manage trap-logging file-size set 1000
#manage trap-logging view-log /*查看日志
#manage trap-logging clear-log /*清除日志
HNCS-PC-IDC-SSL02-8018#manage trap-logging view-log
14452 warning Fan failure 24-11-2014 1.3.6.1.4.1.89.
was detected. 04:51:47 7
1 fan is not
operational
三、查看风扇的工作状态
#system internal fans